TY - JOUR A1 - Teitelbaum, Eric A1 - Alsaad, Hayder A1 - Aviv, Dorit A1 - Kim, Alexander A1 - Völker, Conrad A1 - Meggers, Forrest A1 - Pantelic, Jovan T1 - Addressing a systematic error correcting for free and mixed convection when measuring mean radiant temperature with globe thermometers JF - Scientific reports N2 - It is widely accepted that most people spend the majority of their lives indoors. Most individuals do not realize that while indoors, roughly half of heat exchange affecting their thermal comfort is in the form of thermal infrared radiation. We show that while researchers have been aware of its thermal comfort significance over the past century, systemic error has crept into the most common evaluation techniques, preventing adequate characterization of the radiant environment. Measuring and characterizing radiant heat transfer is a critical component of both building energy efficiency and occupant thermal comfort and productivity. Globe thermometers are typically used to measure mean radiant temperature (MRT), a commonly used metric for accounting for the radiant effects of an environment at a point in space. In this paper we extend previous field work to a controlled laboratory setting to (1) rigorously demonstrate that existing correction factors used in the American Society of Heating Ventilation and Air-conditioning Engineers (ASHRAE) Standard 55 or ISO7726 for using globe thermometers to quantify MRT are not sufficient; (2) develop a correction to improve the use of globe thermometers to address problems in the current standards; and (3) show that mean radiant temperature measured with ping-pong ball-sized globe thermometers is not reliable due to a stochastic convective bias. We also provide an analysis of the maximum precision of globe sensors themselves, a piece missing from the domain in contemporary literature. KW - Strahlungstemperatur KW - Mean radiant temperature KW - Globe thermometers KW - Indoor environment KW - Thermal comfort KW - Measurements KW - OA-Publikationsfonds2022 Y1 - 2022 U6 - http://nbn-resolving.de/urn/resolver.pl?urn:nbn:de:gbv:wim2-20220509-46363 UR - https://www.nature.com/articles/s41598-022-10172-5#citeas VL - 2022 IS - Volume 12, article 6473 PB - Springer Nature CY - London ER - TY - JOUR A1 - Becher, Lia A1 - Völker, Conrad A1 - Rodehorst, Volker A1 - Kuhne, Michael T1 - Background-oriented schlieren technique for two-dimensional visualization of convective indoor air flows JF - Optics and Lasers in Engineering N2 - This article focuses on further developments of the background-oriented schlieren (BOS) technique to visualize convective indoor air flow, which is usually defined by very small density gradients. Since the light rays deflect when passing through fluids with different densities, BOS can detect the resulting refractive index gradients as integration along a line of sight. In this paper, the BOS technique is used to yield a two-dimensional visualization of small density gradients. The novelty of the described method is the implementation of a highly sensitive BOS setup to visualize the ascending thermal plume from a heated thermal manikin with temperature differences of minimum 1 K. To guarantee steady boundary conditions, the thermal manikin was seated in a climate laboratory. For the experimental investigations, a high-resolution DLSR camera was used capturing a large field of view with sufficient detail accuracy. Several parameters such as various backgrounds, focal lengths, room air temperatures, and distances between the object of investigation, camera, and structured background were tested to find the most suitable parameters to visualize convective indoor air flow. Besides these measurements, this paper presents the analyzing method using cross-correlation algorithms and finally the results of visualizing the convective indoor air flow with BOS. The highly sensitive BOS setup presented in this article complements the commonly used invasive methods that highly influence weak air flows. KW - Raumklima KW - Raumluftströmungen KW - Flow visualization KW - Convective indoor air flow KW - Background-oriented schlieren KW - Human thermal plume KW - Cross-correlation Y1 - 2020 U6 - http://nbn-resolving.de/urn/resolver.pl?urn:nbn:de:gbv:wim2-20220810-46972 N1 - This article is published by Elsevier in Optics and Lasers in Engineering 134 (2020) 106282 and may be found at https://doi.org/10.1016/j.optlaseng.2020.106282 Copyright © 2020 Elsevier Ltd. All rights reserved. This article may be downloaded for personal use only. Any other use requires prior permission of the authors and Elsevier Ltd. VL - 2020 IS - Volume 134, article 106282 ER - TY - JOUR A1 - Alsaad, Hayder A1 - Völker, Conrad T1 - Could the ductless personalized ventilation be an alternative to the regular ducted personalized ventilation? JF - Indoor Air N2 - This study investigates the performance of two systems: personalized ventilation (PV) and ductless personalized ventilation (DPV). Even though the literature indicates a compelling performance of PV, it is not often used in practice due to its impracticality. Therefore, the present study assesses the possibility of replacing the inflexible PV with DPV in office rooms equipped with displacement ventilation (DV) in the summer season. Numerical simulations were utilized to evaluate the inhaled concentration of pollutants when PV and DPV are used. The systems were compared in a simulated office with two occupants: a susceptible occupant and a source occupant. Three types of pollution were simulated: exhaled infectious air, dermally emitted contamination, and room contamination from a passive source. Results indicated that PV improved the inhaled air quality regardless of the location of the pollution source; a higher PV supply flow rate positively impacted the inhaled air quality. Contrarily, the performance of DPV was highly sensitive to the source location and the personalized flow rate. A higher DPV flow rate tends to decrease the inhaled air quality due to increased mixing of pollutants in the room. Moreover, both systems achieved better results when the personalized system of the source occupant was switched off. KW - Strömungsmechanik KW - Kontamination KW - Belüftung KW - Luftqualität KW - computational fluid dynamics KW - cross-contamination KW - ductless personalized ventilation KW - indoor air quality KW - tracer gas Y1 - 2020 U6 - http://nbn-resolving.de/urn/resolver.pl?urn:nbn:de:gbv:wim2-20200805-42072 UR - https://onlinelibrary.wiley.com/doi/full/10.1111/ina.12720 VL - 2020 PB - John Wiley & Sons Ltd ER - TY - JOUR A1 - Alsaad, Hayder A1 - Völker, Conrad T1 - Der Kühlungseffekt der personalisierten Lüftung T1 - The cooling effect of personalized ventilation systems JF - Bauphysik N2 - Personalisierte Lüftung (PL) kann die thermische Behaglichkeit sowie die Qualität der eingeatmeten Atemluft verbessern, in dem jedem Arbeitsplatz Frischluft separat zugeführt wird. In diesem Beitrag wird die Wirkung der PL auf die thermische Behaglichkeit der Nutzer unter sommerlichen Randbedingungen untersucht. Hierfür wurden zwei Ansätze zur Bewertung des Kühlungseffekts der PL untersucht: basierend auf (1) der äquivalenten Temperatur und (2) dem thermischen Empfinden. Grundlage der Auswertung sind in einer Klimakammer gemessene sowie numerisch simulierte Daten. Vor der Durchführung der Simulationen wurde das numerische Modell zunächst anhand der gemessenen Daten validiert. Die Ergebnisse zeigen, dass der Ansatz basierend auf dem thermischen Empfinden zur Evaluierung des Kühlungseffekts der PL sinnvoller sein kann, da bei diesem die komplexen physiologischen Faktoren besser berücksichtigt werden. N2 - Personalized ventilation (PV) can improve thermal comfort and inhaled air quality by supplying air to each workstation separately. This study investigates the impact of PV on the thermal state of the users under summer boundary conditions. Two approaches to evaluating the cooling effect of PV were investigated, based on equivalent temperature and based on thermal sensation. Both approaches implemented measured and simulated values of the cooling effect of PV. Before conducting the simulations, the numerical model was first validated against measured data collected in a climate chamber equipped with a thermal manikin. Results indicated that the thermal sensation approach can be more suitable for evaluating the cooling effect of PV due to the complex physiological factors it considers. KW - Lüftung KW - Strömung KW - Raumklima KW - Temperatur KW - personalized ventilation KW - computational fluid dynamics KW - Simulation KW - personalisierte Lüftung KW - äquivalente Temperatur KW - thermisches Empfinden Y1 - 2020 U6 - http://nbn-resolving.de/urn/resolver.pl?urn:nbn:de:gbv:wim2-20201020-42723 UR - https://onlinelibrary.wiley.com/doi/abs/10.1002/bapi.202000018 N1 - © 2020 Ernst & Sohn Verlag für Architektur und technische Wissenschaften GmbH & Co. KG, Berlin. Dieser Artikel kann für den persönlichen Gebrauch heruntergeladen werden. Andere Verwendungen bedürfen der vorherigen Zustimmung der Autoren und des Verlags Ernst & Sohn. Der folgende Artikel erschien in der Bauphysik 42 (2020), Heft 5, 218-225, DOI: 10.1002/bapi.202000018 VL - 2020 IS - volume 42, issue 5 SP - 218 EP - 225 PB - Ernst & Sohn bei John Wiley & Sons CY - Hoboken ER - TY - JOUR A1 - Pollack, Moritz A1 - Lück, Andrea A1 - Wolf, Mario A1 - Kraft, Eckhard A1 - Völker, Conrad T1 - Energy and Business Synergy: Leveraging Biogenic Resources from Agriculture, Waste, and Wastewater in German Rural Areas JF - Sustainability N2 - The imperative to transform current energy provisions is widely acknowledged. However, scant attention has hitherto been directed toward rural municipalities and their innate resources, notably biogenic resources. In this paper, a methodological framework is developed to interconnect resources from waste, wastewater, and agricultural domains for energy utilization. This entails cataloging existing resources, delineating their potential via quantitative assessments utilizing diverse technologies, and encapsulating them in a conceptual model. The formulated models underwent iterative evaluation with engagement from diverse stakeholders. Consequently, 3 main concepts, complemented by 72 sub-concepts, were delineated, all fostering positive contributions to climate protection and providing heat supply in the rural study area. The outcomes’ replicability is underscored by the study area’s generic structure and the employed methodology. Through these inquiries, a framework for the requisite energy transition, with a pronounced emphasis on the coupling of waste, wastewater, and agriculture sectors in rural environments, is robustly analyzed. KW - Energiewende KW - Energieplanung KW - Abfallwirtschaft KW - organischer Abfall KW - Biomasse KW - Regionalentwicklung KW - biogene Abfallstoffe KW - Abwassermanagement KW - OA-Publikationsfonds2023 Y1 - 2023 U6 - http://nbn-resolving.de/urn/resolver.pl?urn:nbn:de:gbv:wim2-20231222-65172 UR - https://www.mdpi.com/2071-1050/15/24/16573 VL - 2023 IS - volume 15, issue 24, article 16573 SP - 1 EP - 25 PB - MDPI CY - Basel ER - TY - JOUR A1 - Alsaad, Hayder A1 - Hartmann, Maria A1 - Hilbel, Rebecca A1 - Völker, Conrad T1 - ENVI-met validation data accompanied with simulation data of the impact of facade greening on the urban microclimate JF - Data in Brief N2 - This dataset consists mainly of two subsets. The first subset includes measurements and simulation data conducted to validate the simulation tool ENVI-met. The measurements were conducted at the campus of the Bauhaus-University Weimar in Weimar, Germany and consisted of recording exterior air temperature, globe temperature, relative humidity, and wind velocity at 1.5 m at four points on four different days. After the measurements, the geometry of the campus was modelled and meshed; the simulations were conducted using the weather data of the measurements days with the aim of investigating the accuracy of the model. The second data subset consists of ENVI-met simulation data of the potential of facade greening in improving the outdoor environment and the indoor air temperature during heatwaves in Central European cities. The data consist of the boundary conditions and the simulation output of two simulation models: with and without facade greening. The geometry of the models corresponded to a residential buildings district in Stuttgart, Germany. The simulation output consisted of exterior air temperature, mean radiant temperature, relative humidity, and wind velocity at 12 different probe points in the model in addition to the indoor air temperature of an exemplary building. The dataset presents both vertical profiles of the probed parameters as well as the time series output of the five-day simulation duration. Both data subsets correspond to the investigations presented in the co-submitted article [1]. KW - Messung KW - Measurements KW - Simulations KW - ENVI-met KW - Living wall KW - Green facade KW - Simulation KW - OA-Publikationsfonds2022 Y1 - 2022 U6 - http://nbn-resolving.de/urn/resolver.pl?urn:nbn:de:gbv:wim2-20220511-46455 UR - https://www.sciencedirect.com/science/article/pii/S2352340922004048#! VL - 2022 IS - Volume 42, article 108200 SP - 1 EP - 13 PB - Elsevier CY - Amsterdam ER - TY - JOUR A1 - Alsaad, Hayder A1 - Hartmann, Maria A1 - Völker, Conrad T1 - Hygrothermal simulation data of a living wall system for decentralized greywater treatment JF - Data in Brief N2 - This dataset presents the numerical analysis of the heat and moisture transport through a facade equipped with a living wall system designated for greywater treatment. While such greening systems provide many environmental benefits, they involve pumping large quantities of water onto the wall assembly, which can increase the risk of moisture in the wall as well as impaired energetic performance due to increased thermal conductivity with increased moisture content in the building materials. This dataset was acquired through numerical simulation using the coupling of two simulation tools, namely Envi-Met and Delphin. This coupling was used to include the complex role the plants play in shaping the near-wall environmental parameters in the hygrothermal simulations. Four different wall assemblies were investigated, each assembly was assessed twice: with and without the living wall. The presented data include the input and output parameters of the simulations, which were presented in the co-submitted article [1]. KW - Kupplung KW - Feuchteleitung KW - Heat transport KW - Moisture transport KW - Living wall KW - Wärmeübertragung KW - coupling KW - ENVI-Met KW - Delphin KW - OA-Publikationsfonds2022 Y1 - 2022 U6 - http://nbn-resolving.de/urn/resolver.pl?urn:nbn:de:gbv:wim2-20220106-45483 UR - https://www.sciencedirect.com/science/article/pii/S2352340921010167?via%3Dihub VL - 2022 IS - volume 40, article 107741 PB - Elsevier CY - Amsterdam ER - TY - JOUR A1 - Dokhanchi, Najmeh Sadat A1 - Arnold, Jörg A1 - Vogel, Albert A1 - Völker, Conrad T1 - Measurement of indoor air temperature distribution using acoustic travel-time tomography: Optimization of transducers location and sound-ray coverage of the room JF - Measurement N2 - Acoustic travel-time TOMography (ATOM) allows the measurement and reconstruction of air temperature distributions. Due to limiting factors, such as the challenge of travel-time estimation of the early reflections in the room impulse response, which heavily depends on the position of transducers inside the measurement area, ATOM is applied mainly outdoors. To apply ATOM in buildings, this paper presents a numerical solution to optimize the positions of transducers. This optimization avoids reflection overlaps, leading to distinguishable travel-times in the impulse response reflectogram. To increase the accuracy of the measured temperature within tomographic voxels, an additional function is employed to the proposed numerical method to minimize the number of sound-path-free voxels, ensuring the best sound-ray coverage of the room. Subsequently, an experimental set-up has been performed to verify the proposed numerical method. The results indicate the positive impact of the optimal positions of transducers on the distribution of ATOM-temperatures. KW - Bauphysik KW - Bauklimatik KW - Akustische Laufzeit-Tomographie Y1 - 2020 U6 - http://nbn-resolving.de/urn/resolver.pl?urn:nbn:de:gbv:wim2-20220524-46473 UR - https://www.sciencedirect.com/science/article/abs/pii/S0263224120304723?via%3Dihub VL - 2020 IS - Volume 164, article 107934 PB - Elsevier CY - Amsterdam ER - TY - JOUR A1 - Völker, Conrad A1 - Mämpel, Silvio A1 - Kornadt, Oliver T1 - Measuring the human body’s micro‐climate using a thermal manikin JF - Indoor Air N2 - The human body is surrounded by a micro‐climate which results from its convective release of heat. In this study, the air temperature and flow velocity of this micro‐climate were measured in a climate chamber at various room temperatures, using a thermal manikin simulating the heat release of the human being. Different techniques (Particle Streak Tracking, thermography, anemometry, and thermistors) were used for measurement and visualization. The manikin surface temperature was adjusted to the particular indoor climate based on simulations with a thermoregulation model (UCBerkeley Thermal Comfort Model). We found that generally, the micro‐climate is thinner at the lower part of the torso, but expands going up. At the head, there is a relatively thick thermal layer, which results in an ascending plume above the head. However, the micro‐climate shape strongly depends not only on the body segment, but also on boundary conditions: the higher the temperature difference between the surface temperature of the manikin and the air temperature, the faster the air flow in the micro‐climate. Finally, convective heat transfer coefficients strongly increase with falling room temperature, while radiative heat transfer coefficients decrease. The type of body segment strongly influences the convective heat transfer coefficient, while only minimally influencing the radiative heat transfer coefficient. KW - Raumklima KW - Mikroklima KW - Wärmeübertragung KW - Strömungsmechanik KW - thermal manikin KW - climate chamber KW - micro climate KW - heat transfer coefficient KW - CFD KW - thermography Y1 - 2014 U6 - http://nbn-resolving.de/urn/resolver.pl?urn:nbn:de:gbv:wim2-20181025-38153 UR - https://onlinelibrary.wiley.com/doi/abs/10.1111/ina.12112 N1 - This is the peer reviewed version of the following article: "Measuring the human body’s micro‐climate using a thermal manikin", which has been published in final form at https://doi.org/10.1111/ina.12112. This article may be used for non-commercial purposes in accordance with Wiley Terms and Conditions for Use of Self-Archived Versions. IS - 24, 6 SP - 567 EP - 579 ER - TY - JOUR A1 - Völker, Conrad A1 - Beckmann, Julia A1 - Koehlmann, Sandra A1 - Kornadt, Oliver T1 - Occupant requirements in residential buildings – an empirical study and a theoretical model JF - Advances in Building Energy Research N2 - Occupant needs with regard to residential buildings are not well known due to a lack of representative scientific studies. To improve the lack of data, a large scale study was carried out using a Post Occupancy Evaluation of 1,416 building occupants. Several criteria describing the needs of occupants were evaluated with regard to their subjective level of relevance. Additionally, we investigated the degree to which deficiencies subjectively exist, and the degree to which occupants were able to accept them. From the data obtained, a hierarchy of criteria was created. It was found that building occupants ranked the physiological needs of air quality and thermal comfort the highest. Health hazards such as mould and contaminated building materials were unacceptable for occupants, while other deficiencies were more likely to be tolerated. Occupant satisfaction was also investigated. We found that most occupants can be classified as satisfied, although some differences do exist between different populations. To explain the relationship between the constructs of what we call relevance, acceptance, deficiency and satisfaction, we then created an explanatory model. Using correlation and regression analysis, the validity of the model was then confirmed by applying the collected data. The results of the study are both relevant in shaping further research and in providing guidance on how to maximize tenant satisfaction in real estate management. KW - Post Occupancy Evaluation KW - Gebäude KW - Benutzung KW - occupant requirements KW - occupant satisfaction KW - residential buildings KW - housing KW - questionnaire Y1 - 2013 U6 - http://nbn-resolving.de/urn/resolver.pl?urn:nbn:de:gbv:wim2-20181015-38137 UR - https://www.tandfonline.com/doi/abs/10.1080/17512549.2012.749808 N1 - This is an Accepted Manuscript of an article published by Taylor & Francis in Advances in Building Energy Research on 29/01/2013, available online: https://www.tandfonline.com/doi/abs/10.1080/17512549.2012.749808. IS - 7 (1) SP - 35 EP - 50 ER -