@phdthesis{Dokhanchi, author = {Dokhanchi, Najmeh Sadat}, title = {Measurement of the Indoor Air Temperature Distribution using Acoustic Travel-Time Tomography}, isbn = {978-3-00-075344-2 (print)}, doi = {10.25643/bauhaus-universitaet.4956}, url = {http://nbn-resolving.de/urn:nbn:de:gbv:wim2-20230414-49567}, school = {Bauhaus-Universit{\"a}t Weimar}, pages = {155}, abstract = {One of the main criteria determining the thermal comfort of occupants is the air temperature. To monitor this parameter, a thermostat is traditionally mounted in the indoor environment for instance in office rooms in the workplaces, or directly on the radiator or in another location in a room. One of the drawbacks of this conventional method is the measurement at a certain location instead of the temperature distribution in the entire room including the occupant zone. As a result, the climatic conditions measured at the thermostat point may differ from those at the user's location. This not only negatively impacts the thermal comfort assessment but also leads to a waste of energy due to unnecessary heating and cooling. Moreover, for measuring the distribution of the air temperature under laboratory conditions, multiple thermal sensors should be installed in the area under investigation. This requires high effort in both installation and expense. To overcome the shortcomings of traditional sensors, Acoustic travel-time TOMography (ATOM) offers an alternative based on measuring the transmission sound velocity signals. The basis of the ATOM technique is the first-order dependency of the sound velocity on the medium's temperature. The average sound velocity, along the propagation paths, can be determined by travel-times estimation of a defined acoustic signal between transducers. After the travel-times collection, the room is divided into several volumetric grid cells, i.e. voxels, whose sizes are defined depending on the dimension of the room and the number of sound paths. Accordingly, the spatial air temperature in each voxel can be determined using a suitable tomographic algorithm. Recent studies indicate that despite the great potential of this technique to detect room climate, few experiments have been conducted. This thesis aims to develop the ATOM technique for indoor climatic applications while coupling the analysis methods of tomography and room acoustics. The method developed in this thesis uses high-energy early reflections in addition to the direct paths between transducers for travel time estimation. In this way, reflections can provide multiple sound paths that allow the room coverage to be maintained even when a few or even only one transmitter and receiver are used. In the development of the ATOM measurement system, several approaches have been employed, including the development of numerical methods and simulations and conducting experimental measurements, each of which has contributed to the improvement of the system's accuracy. In order to effectively separate the early reflections and ensure adequate coverage of the room with sound paths, a numerical method was developed based on the optimization of the coordinates of the sound transducers in the test room. The validation of the optimal positioning method shows that the reconstructed temperatures were significantly improved by placing the transducers at the optimal coordinates derived from the developed numerical method. The other numerical method developed is related to the selection of the travel times of the early reflections. Accordingly, the detection of the travel times has been improved by adjusting the lengths of the multiple analysis time-windows according to the individual travel times in the reflectogram of the room impulse response. This can reduce the probability of trapping faulty travel times in the analysis time-windows. The simulation model used in this thesis is based on the image source model (ISM) method for simulating the theoretical travel times of early reflection sound paths. The simulation model was developed to simulate the theoretical travel times up to third-order reflections. The empirical measurements were carried out in the climate lab of the Chair of Building Physics under different boundary conditions, i.e., combinations of different room air temperatures under both steady-state and transient conditions, and different measurement setups. With the measurements under controllable conditions in the climate lab, the validity of the developed numerical methods was confirmed. In this thesis, the performance of the ATOM measurement system was evaluated using two measurement setups. The setup for the initial investigations consists of an omnidirectional receiver and a near omnidirectional sound source, keeping the number of transducers as few as possible. This has led to accurately identify the sources of error that could occur in each part of the measuring system. The second measurement setup consists of two directional sound sources and one omnidirectional receiver. This arrangement of transducers allowed a higher number of well-detected travel times for tomography reconstruction, a better travel time estimation due to the directivity of the sound source, and better space utilization. Furthermore, this new measurement setup was tested to determine an optimal selection of the excitation signal. The results showed that for the utilized setup, a linear chirp signal with a frequency range of 200 - 4000 Hz and a signal duration of t = 1 s represents an optimal selection with respect to the reliability of the measured travel times and higher signal-to-noise ratio (SNR). To evaluate the performance of the measuring setups, the ATOM temperatures were always compared with the temperatures of high-resolution NTC thermistors with an accuracy of ±0.2 K. The entire measurement program, including acoustic measurements, simulation, signal processing, and visualization of measurement results are performed in MATLAB software. In addition, to reduce the uncertainty of the positioning of the transducers, the acoustic centre of the loudspeaker was determined experimentally for three types of excitation signals, namely MLS (maximum length sequence) signals with different lengths and duration, linear and logarithmic chirp signals with different defined frequency ranges. For this purpose, the climate lab was converted into a fully anechoic chamber by attaching absorption panels to the entire surfaces of the room. The measurement results indicated that the measurement of the acoustic centre of the sound source significantly reduces the displacement error of the transducer position. Moreover, to measure the air temperature in an occupied room, an algorithm was developed that can convert distorted signals into pure reference signals using an adaptive filter. The measurement results confirm the validity of the approach for a temperature interval of 4 K inside the climate lab. Accordingly, the accuracy of the reconstructed temperatures indicated that ATOM is very suitable for measuring the air temperature distribution in rooms.}, subject = {Bauphysik}, language = {en} } @phdthesis{Hoffmann2006, author = {Hoffmann, Sabine}, title = {Numerische und experimentelle Untersuchung von Phasen{\"u}bergangsmaterialien zur Reduktion hoher sommerlicher Raumtemperaturen}, doi = {10.25643/bauhaus-universitaet.823}, url = {http://nbn-resolving.de/urn:nbn:de:gbv:wim2-20070709-8790}, school = {Bauhaus-Universit{\"a}t Weimar}, year = {2006}, abstract = {Moderne B{\"u}roarchitektur mit R{\"a}umen in Leichtbauweise und großen transparenten Fassa-denanteilen versch{\"a}rft im Zusammenwirken mit hohen internen Lasten die Problematik der sommerlichen {\"U}berhitzung in Geb{\"a}uden. Phasen{\"u}bergangsmaterialien (PCM: phase change materials) stellen eine interessante M{\"o}glichkeit dar, sommerliche {\"U}berhitzung in Geb{\"a}uden ohne aufw{\"a}ndige Anlagentechnik wie beispielsweise Klimaanlagen zu reduzieren. Der thermische Komfort in R{\"a}umen, die mit einem PCM-Putz ausgestattet sind, kann signifikant erh{\"o}ht werden. Die Arbeit untersucht Anwendungsm{\"o}glichkeiten und Optimierungspotential eines PCM-Putzes auf experimentelle und numerische Weise. Zur Untersuchung des PCM-Putzes wurden materialtechnische und experimentelle sowie numerische und numerisch-analytische Methoden eingesetzt. Die Kenntnis der thermischen Parameter des PCM-Putzes ist unabl{\"a}ssig f{\"u}r die Berechnung der m{\"o}glichen Temperaturreduktionen. Zur Bestimmung der Latentw{\"a}rme, des qualitativen Schmelz- und Erstarrungsprozesses sowie des Temperaturintervalls, in dem der Phasen{\"u}bergang stattfindet, wurden Messungen mit einem Differential Scanning Calorimeter (DSC) durchgef{\"u}hrt. F{\"u}r die experimentelle Untersuchung des PCM-Putzes wurden zwei identische Testr{\"a}ume in Leichtbauweise erstellt. Die R{\"a}ume wurden im Verifikationsobjekt „Eiermannbau" des Sonderforschungsbereiches SFB 524 der Bauhaus-Universit{\"a}t Weimar gemessen. Nach der {\"U}berpr{\"u}fung, dass sich beide R{\"a}ume thermisch gleich verhalten, wurde ein Raum mit dem PCM-Putz und der zweite Raum mit einem vergleichbaren Innenputz ohne PCM verputzt. Thermoelemente zur Temperaturmessung im Bauteil, an der Oberfl{\"a}che und zur Raumlufttemperaturbestimmung wurden angebracht und mit einer Messwerterfassungsanlage verbunden. Der Verlauf der Außenlufttemperatur und die Globalstrahlung am Standort der Versuchsr{\"a}ume wurden aufgezeichnet, um einen Klimadatensatz zu erstellen. F{\"u}r die Berechnung der Temperaturverteilung in einem PCM-Bauteil mit kontinuierlichem Phasen{\"u}bergang existiert keine geschlossene analytische L{\"o}sung. Daher wurde ein numerischer Ansatz gew{\"a}hlt, bei dem der Phasen{\"u}bergang im Temperaturbereich T1 bis T2 mit Hilfe einer temperaturabh{\"a}ngigen W{\"a}rmekapazit{\"a}t c(T) innerhalb der erweiterten Fou-rier'schen W{\"a}rmeleitungsgleichung dargestellt wird. Die Funktion c(T) wird auf Basis der DSC-Messungen bestimmt. Die Modellierung erfolgte mit einem Finite-Differenzen-Verfahren auf Grundlage der Fourier'schen W{\"a}rmeleitungsgleichung. Im Rahmen der Arbeit wurde ein PCM-Modul entwickelt, das in ein Geb{\"a}udesimulationsprogramm implementiert wurde. Mit dem neuen Modul lassen sich sowohl die Temperaturverl{\"a}ufe in einem PCM-Bauteil wie auch seine Wechselwirkung mit dem Raumklima darstellen. Eine Validierung des entwickelten PCM-Moduls anhand von zahlreichen experimentellen Daten der Versuchsr{\"a}ume wurde f{\"u}r das PCM-Modul erfolgreich durchgef{\"u}hrt. Sommerliche {\"U}berhitzungsstunden k{\"o}nnen durch PCM in Wand- und Deckenelementen deutlich reduziert werden. Der PCM-Putz eignet sich vor allem f{\"u}r Anwendungen in Leichtbauten wie z.B. moderne B{\"u}ror{\"a}ume. In R{\"a}umen, in denen bereits eine ausreichende thermische Masse vorhanden ist, ist die Temperaturreduktion durch PCM nur gering. Kann das PCM w{\"a}hrend der Nachtstunden nicht erstarren, ersch{\"o}pft sich seine F{\"a}higkeit zur Latentw{\"a}rmespeicherung. Erh{\"o}hte Nachtl{\"u}ftung f{\"u}hrt bei entsprechend niedrigen Außentemperaturen zu h{\"o}herem W{\"a}rme{\"u}bergang und kann damit zur besseren Entladung des PCM beitragen. Im Rahmen der Dissertation konnten Aussagen zur idealen Phasen{\"u}bergangstemperatur in Abh{\"a}ngigkeit des verwendeten Materials und der Schichtdicke getroffen werden. Die Reduktion der Oberfl{\"a}chentemperaturen, die sich bei Einsatz eines PCM-Putzes unter geeigneten Randbedingungen ergibt, betr{\"a}gt 2.0 - 3.5 K f{\"u}r eine Putzschicht von 1 cm und 3.0 - 5.0 K f{\"u}r eine Putzschicht von 3 cm. Diese Werte wurden sowohl numerisch als auch durch experimentelle Untersuchungen ermittelt. Die Reduktion der Lufttemperaturen aufgrund einer Konditionierung des Raumes mit PCM-Putz betr{\"a}gt bei geeigneten thermischen Verh{\"a}ltnissen ca. 1.0 - 2.5 K f{\"u}r eine Putzschicht von 1 cm und 2.0 - 3.0 K f{\"u}r eine Putzschicht von 3 cm. Die operative Temperatur als wichtiger Komfortparameter kann durch den Einsatz des PCM-Putzes um bis zu 4 K gesenkt werden. Damit l{\"a}sst sich mit Hilfe eines PCM-Putzes die thermische Behaglichkeit in einem Raum deutlich erh{\"o}hen.}, subject = {Bauphysik}, language = {de} }